Technical Details
– Universal input accepts Thermocouples J, K, T, E, N, R, S, B and Pt100, Pt1000 and NTC RTD with programmable working range
– Loop powered 4-20 mA output
– Linearized 4 to 20 mA or 20 to 4 mA output
– Cold junction compensation for thermocouples
– Cable resistance compensation on 3 or 4 wires Pt100 connection
– USB micro-B port allows direct PC or smartphone connection for configuration
– Free Windows configuration software
– Free Android configuration app
– Power supply: 10 to 35 Vdc
– RTD Typical Accuracy: ± 0.1 % for Pt100 and Pt1000 and ± 0.3 °C for NTC
– Thermocouple and mV Typical Accuracy: ± 0.1 %
– Temperature effect: Smaller than 0.16 % / 25 °C
– Working temperature: -40 to +85 °C (-40 to 185 °F)
– Sensor break detection according to NAMUR NE43 recommendations
– Dimensions: 43.5 mm x 20.5 mm (1.71 in x 0.80 in) D x H