Technical Details
– Input Type: TC J, K, T, N, R, S, B, E, Pt100 0-20 mA, 4-20 mA, 0-50 mV, 0-5 Vdc, 0-10 Vdc
– Accuracy: Thermocouples J, K, T: 0.25 % of span ±1 °C; Thermocouples N, R, S, B: 0.25 % of span ± 3 °C; Pt100, 0-20 mA, 4-20 mA, 0-5 Vdc, 0-10 Vdc: 0.2 % of span
– Input Resolution: 32767 levels (15 bits)
– Sampling Rate: 55 samples per second
– Analog Output: 0-20 mA or 4-20 mA
– Output Resolution: 31000 levels
– Control Type: PID, PI, PD, P; On/Off
– Control Action: Heat or Cool
– Control Output: Type SSR Pulse; 4-20 mA control; Relay
– Open Sensor Detection: Loop Break / Heater breaker detection
– Alarm Types: Minimum, Maximum, Differential, Differential, Low, Differential High, Open Sensor, Ramp and Soak Event
– Optional: Relay, Two Digital Inputs or Outputs, RS-485, Heater break detection
– Communication: RS485 Modbus optional
– Ramp and Soak programs: 20 programs with 9 segments each
Safety: Password protected configuration
– Configuration Interface: USB type Mini B (powered)
– Power Supply: 100-240 Vac/dc; 12-24 Vdc
– Maximum Consumption: 9 VA
– Front Pannel: IP65 ; Polycarbonate (PC) UL94 V-2
– 48 x 48 x 110 mm (DIN 1/16); ABS+PC UL94 V-0
– Enclosure: IP20
– Operating Conditions: 5 to 50 °C (41 to 122 °F) and 0 to 80 % RH
– Approvals: CE, RoHS, Reach, UL, and cUL